Heat Shrinkable Terminations Suitable for 3 Core Paper Insulated Lead Covered MIND Cables Up to 36kV

CPO/I-1112, CPO/I-1524, CPO/I-3336-SERIES

Heat-Shrink-XLPE-Termination-Main-2

Product Description

Compaq Heat Shrinkable Indoor/Outdoor Terminations are designed for 3 Core Paper Insulated Lead Covered MIND Cables Up to 36 kV. The design has been focused to provide the basic important functions required for medium voltage power cable accessories including the electric performance, stress relief measure, environmental seal, mechanical fatigues and other related performance parameters laid down in different countries for various service conditions. Compaq Heat shrink terminations are suitable for indoor (switch gear, cable box, transformer, motor type) and outdoor (pole mounted) terminating of 3 core cable. They are also suitable for 3 Core Paper Insulated Lead Covered MIND Cables Up to 36 kV.

Features

  • Durability
  • High tensile strength
  • Longer service life
  • Resistance against corrosion
  • Suitable for Mechanical shear head Lugs & Compression Lugs.

SPECIFICATIONS AND STANDARDS:

Meets the requirement of IS: 13573 (2011), IEC 60502, IEEE 48, 404, CENELEC HD 629-1 & other applicable international quality.

Test Description
Requirements
Technical Values
12KV
24KV
36KV
12KV
24KV
36KV
A.C Voltage withstand test (Dry) 35kV/1 minute 50kV/1 minute 75kV/1 minute Pass Pass Pass
D.C Voltage withstand test 40Kv/30 minutes 96KV/15 minutes 144KV/30 minutes Pass Pass Pass
Lightning impulse withstand voltage 75kV 125kV 170kV >75kV >125kV >170kV
Humidity test (indoor)
300 hours at 1.25 U ̥ (8kV rms)
Withstood
Salt fog test (outdoor)
1000 hours at 1.25 U ̥ (8kVrms)
Withstood

SELECTION GUIDE:

CPO / I 1112 – SERIES

Cable Size(sq. mm)
Kit Code
Indoor
Outdoor
16-35
CPI – 11
CPO – 11
50-95
CPI – 12
CPO – 12
120-185
CPI – 13
CPO – 13
240-400
CPI – 14
CPO – 14
500
CPI – 15
CPO – 15

SELECTION GUIDE:

CPO / I 1524 – SERIES

Cable Size(sq. mm)
Kit Code
Indoor
Outdoor
25-50
CPI – 21
CPO – 21
70-120
CPI – 22
CPO – 22
150-240
CPI – 23
CPO – 23
300-500
CPI – 24
CPO – 24

SELECTION GUIDE:

CPO / I 3336 – SERIES

Cable Size(sq. mm)
Kit Code
Indoor
Outdoor
35-70
CPI – 31
CPO – 31
95-170
CPI – 32
CPO – 32
185-300
CPI – 33
CPO – 33
185-300
CPI – 33
CPO – 33
400-500
CPI – 34
CPO – 34

SIGN-UP FOR UPDATES !