COLD SHRINK 1 & 3 CORE TERMINATION SUITABLE FOR XLPE/EPR/PVC/ ELASTOMERIC & PILC CABLES

CCSI/CCSO - 11/22/33kV SERIES

6/10(12)kV, 6.35/11(12)kV, 8.75/15(17.5)kV, 12/20(24)kV, 12.7/22(24)kV, 19/33(36)kV

Cold Shrink Main

Product Description

Compaq cold shrink terminations make use of liquid silicon rubber material to ensure a reliable performance. The terminations developed by Compaq can meet a wide range of applications and can also accommodate all types of conductors and cables used in the networks.

On a removable spiral core, a series of pre stretched components are assembled and these units are utilized in Cold Shrink Terminations. After positioning the tube for installation over inline connection, the core is taken off, which allows the tube to shrink and form a water proof seal.

Features

  • Easy to install with short installation time.
  • Electrical stress control of the screen cut area using integrated conductive geometrical stress cones.
  • Mechanical Shear Head type & Compression type lugs can be supplied.
  • Nonflammable.

Specification & Standards

Compaq Cold Shrink Termination meets the requirements of IS: 13573 (2011), IEC 60502, IEEE 98, 404, CANELEC HD 629.1.

Text Discription Requirements
Technical Values

12KV 24KV 36KV
A.C Voltage withstand test ( Dry ) 5 minutes at 4.5 U ̥ 35KV 58KV 86KV
A.C Voltage Withstand test ( Wet ) 1 Minutes at 4U ̥
(Only Outdoor Termination)
30KV 51KV 76KV
D.C Voltage Withstand test 15 minutes at 4 U ̥ 48KV 96KV 144KV
Partial discharge test 10 Pc Max. at 1.73 U ̥ <5 Pc upto
12.7 KV
<5 Pc upto
25 KV
<5 Pc upto
33 KV
Impulse voltage withstand test 10 impulse each polarity at 75kV 95kV 125kV 170kV
Thermal Short Circuit ( Screen ) Two short circuit & no visible deterioration Even confirm to more straight condition
Thermal Short Circuit ( Conductor ) Two short circuit & no visible deterioration Even confirm to more straight condition
Dynamic short circuit One short circuit & no visible deterioration Even confirm to more straight condition
Humidity test 300 hours at 1.25 U ̥ Passes
Salt fog test 1000 hours at 1.25 U ̥ Passes

SELECTION GUIDE

12-24-36kV 3Core Indoor Termination

Cable Size
(sq. mm)
Kit Code

12kV 24KV 36KV
50 – 70 CCSI – 11 CCSI – 21 CCSI – 31
95 – 150 CCSI – 12 CCSI – 22 CCSI – 32
185 – 300 CCSI – 13 CCSI – 23 CCSI – 33
400 CCSI – 14 CCSI – 24 CCSI – 34

12-24-36kV 3Core Outdoor Termination

Cable Size
(sq. mm)
Kit Code

12kV 24KV 36KV
50 – 70 CCSO – 11 CCSO – 21 CCSO – 31
95 – 150 CCSO – 12 CCSO – 22 CCSO – 32
185 – 300 CCSO – 13 CCSO – 23 CCSO – 33
400 CCSO – 14 CCSO – 24 CCSO – 34

12-24-36kV 1Core Indoor Termination

Cable Size
(sq. mm)
Kit Code

12kV 24KV 36KV
50 – 70 CCSIS – 11 CCSIS – 21 CCSIS – 31
95 – 150 CCSIS – 12 CCSIS – 22 CCSIS – 32
185 – 300 CCSIS – 13 CCSIS – 23 CCSIS – 33
400 – 630 CCSIS – 14 CCSIS – 24 CCSIS – 34

12-24-36kV 1Core Outdoor Termination

Cable Size
(sq. mm)
Kit Code

12kV 24KV 36KV
50 – 70 CCSOS – 11 CCSOS – 21 CCSOS – 31
95 – 150 CCSOS – 12 CCSOS – 22 CCSOS – 32
185 – 300 CCSOS – 13 CCSOS – 23 CCSOS – 33
400 – 630 CCSOS – 14 CCSOS – 24 CCSOS – 34